| MODEL |
PS100R4MU42 |
PS100R5MU42 |
PS100R6MU42 |
PS100R8MU42 |
PS100R10MU42 |
PS100R12MU42 |
| Rating (kVA) Configurable |
400 |
500 |
600 |
800 |
1000 |
1200 |
| Dimension WxDxH (mm) |
800 x 1000 x 2000 |
800 x 1000 x 2000 (S)
1400 x 1000 x 2000 (F)
|
1400 x 1000 x 2000 (S)
1800 x 1000 x 2000 (F)
|
| Weight (Kg) |
305 (S) 350 (F) |
330 (S) 380 (F) |
350 (S) 410 (F) |
405 (S) 780 (F) |
690 (S) 850 (F) |
760 (S) 920 (F) |
| Bypass |
Feature |
Hot-Swappable Inbuilt Static Bypass Module for Max. Inbuilt Maintenance Bypass Switch
|
| Voltage |
Max. Voltage: + 15% (Optional +5%, +10%, +20%), Min. Voltage: -45% (Optional -10%, -15%, -20% & -30%)
|
| Frequency |
50 / 60 Hz Auto Sensing ± 1Hz, ± 3Hz, ± 5Hz
|
| Overload |
135% Overload Continuous ; >1000% Overload for 100 ms
|
| Monitoring |
7 Inch. Touch Screen Display |
| Nos. of Module |
100kVA x 04 |
100kVA x 05 |
100kVA x 06 |
100kVA x 08 |
100kVA x 10 |
100kVA x 12 |
| Switches & Connections |
Connections - Rectifier Input / Output / Bypass Input / Battery & Switches - Input, Bypass, Output & Maintenance Bypass
|
| MODULE |
PS100M33100 |
| Dimension WxDxH (mm) |
440 x 755 x 130 (3U) |
| Weight (Kg) Each 100kVA |
52.5 Kg |
| INPUT |
| Nominal Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Operating Voltage Range |
138V - 322V AC for 40% Load & 323V - 485V AC for 100% Load
|
| Operating Frequency Range |
40Hz - 70Hz Auto Sensing |
| Power Factor |
≥ 0.99 |
| Harmonic Distortion (THDi) |
≤ 3% |
| Generator Input / Walking |
Support / 0-40 Sec. (Configurable) |
| OUTPUT |
| Output Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Voltage Regulation |
± 1% |
| Power Factor |
1.0 (Unity) |
| Frequency |
Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz (Free Running / Self Clocked Mode)
|
| Crest Factor |
3:1 |
| Harmonic Distortion (THDv) |
≤ 1% |
| Over Load |
≤110% for 60 min, ≤125 % for 10 min, ≤ 150% for 1 min, >150% for 200 ms
|
| Slew Rate |
1 Hz/s |
| Phase Displacement Angle |
120° ± 1° (At 100% Balanced Load) & 120° ± 2° (At 100% Balanced Load)
|
| Transient Response & Response time |
0% to 90 % step load = +/- 5%, < 10 ms (Asynchronized Mode)
|
| Efficiency |
97.1% Dual Conversion Mode, 99.0% ECO Mode
|
| BATTERY |
| Battery Voltage |
± 240V DC Nominal (30 - 50 Nos. Configurable)
|
| SYSTEM FEATURE |
| Self-Diagnostics |
During Power ON and Software Control |
| EPO |
UPS Shut down |
| Transfer Time |
Zero |
| Alarm / Protections |
Short Circuit, Input Under/Over Voltage, Over Temperature, Over Load, DC BUS Under / Over Voltage and Battery low
|
| Event Logging & Statistical Data |
16,384 events on LCD: Over temp, DC Bus Fail, Fan Fail, Fuse Fail, Overload, Short- circuit, Device Fail, Inverter Fail, Rectifier Fail, Bypass Fail, etc
|
| Display |
Touch Screen LCD & LED Indication |
| ENVIRONMENTAL |
| Temperature |
Operating: 0~50°C*, Storage: -25°C ~ 70°C
|
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M (above sea level) without derating, Derating 1% for each additional 100m.
|
| Noise |
<55dBA |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS
|
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
Complying to CE, IEC/EN62040-2; IEC/EN62040-3
|
| COMMUNICATION INTERFACE |
| Standard |
Rack RS232, RS485, Dry Contact |
| Optional |
BMS/ RS485/ SNMP / ModBus / Dry Contact (Output Dry contact : 6 configurable for 21 events including Battery breaker shunt trip, back feed protection, EPO activated etc. & Input Dry contact : 4 / Parallel Port (LBS) / REPO / External Battery Temperature sensor / External switch Breaker status
|
| Monitoring Software |
NetAgent Utility v5.8 / Muser 4000 / Power Manager
|