DSII Series 10~40kVA

High reliability design Double conversion Online design, which makes the output a pure sine wave source with tracking frequency, phase-lock and voltage regulation, low distortion and without power fluctuation interference, providing the load with more comprehensive protection. High reliability during operation Pure online with static bypass technology, provides a strong protection against overload and fault. Built-in manual maintenance bypass,further improves the reliability of continuous operation.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • High reliability design

Double conversion Online design, which makes the output a pure sine wave source with tracking frequency, phase-lock and voltage regulation, low distortion and
without power fluctuation interference, p r o v i d i n g t h e l o a d w i t h m o r e comprehensive protection.

  • High reliability during operation

Pure online with static bypass technology, provides a strong protection against overload and fault. Built-in manual maintenance bypass, further improves the reliability of continuous operation.

  • Strong protection for load

Built-in isolation transformer, strong antiinterference ability, provides more comprehensive protection.

  • Wide input range

The range of AC input voltage is 380V ± 20%, thereby it reduces the battery using frequency and greatly extending the battery life. Wide input frequency range & ensure all type of generator compatible

  • Comprehensive and reliable protection

Self-diagnostic function before start-up, avoid the risks failure. The multi-protections such as overload, short circuit, over temperature, battery under voltage, battery over-charge and so on greatly ensure the system stability and reliability. Built-in static electronic bypass switch. when UPS fail, it can transfer to bypass mode and continue to provide power to load.

  • Adoption of IGBT

Adoption of IGBT inverter & Charger saves energy & coupled with an isolation transformer, enhances the reliability and load adaptability.

  • Strong redundancy/parallel ability (DSII Series)

Same Unit can be directly connected in parallel, increasing the scalability of the system. Non-fixed master-slave relationship: Among several UPS in parallel, the unit
startup first is master UPS , the others are slave UPS. The master and slave can be exchanged. If the inverter of one UPS fail, the UPS will automatically cut off the output, then the load will be powered by remained UPS.

  • User friendly network management

Communication with computer can be realized by RS-232 with corresponding monitoring software. The various parameters can be shown on the communication interface.

  • External SNMP adapter (Optional)

The UPS with remote network management capability can provide real-time data for communication and management through a variety of network management systems.

  • Fully coating PCBAs to withstand harsh environment

The outside cabinet is designed only with locks without any screws and all PCBAs are coated for anti-moisture, anti-electric leakage, anti-dust and anti-corrosion. Its robust design is suitable for harsh environment with high temperature, high humidity, dense dust, salt, or fierce vibration.

MODEL DSII3110L16 DSII3115L16 DSII3120L16 DSII3125L16 DSII3130L16 DSII3120L16 DSII3120L30 DSII3130L20 DSII3140L30
Capacity (kVA) 10 15 20 25 30 20 30 40
INPUT
Voltage Range 380V / 400V / 415V AC ± 20% (3Ph+N+PE)
Frequency Range 50 Hz / 60 Hz ±10% (Auto Sensing)
OUTPUT
Voltage Range 220V / 230V / 240V AC (± 1%)
Frequency Range Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
Power Factor 0.8 Standard, (0.9 Optional)
Crest Factor 3:1
Efficiency 94.0% Dual Conversion Mode, 99.0% ECO Mode
THDv ≤1%
Overload ≤ 125% for 10 Min, ≤ 150% for 1 Min, >150% for 300 ms
BATTERY
Battery voltage 192V DC 240V DC 360V DC
Charging Current (Amp.) 12 Amp. 10 ~ 40 Amp.
SYSTEM FEATURES
Transfer Time Zero
Display LED Utility Status, Inverter, Bypass, Battery Status, UPS Abnormal, Overload and Fault
LCD I/O Voltage, Frequency, Battery Voltage, Load, Temperature and fault
Alarm / Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC BUS Under / Over Voltage and Battery low
Parallel Card (Optional) Yes Yes Yes Yes Yes No Yes Yes Yes
ENVIRONMENT
Temperature Operating: 0~50°C*, Storage: -15°C ~ 60°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise ≤50dBA ≤55dBA
PHYSICAL
Dimension WxDxH (mm) 310x590x870 400x815x1100 300x815x830 405x656x817 432x821x1159
Net Weight (Kg) 115 125 201 230 277 150 145 193 278
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
COMMUNICATION INTERFACE
Standard RS-232
Optional SNMP / ModBus / Dry Contact / USB / RS-485
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000