PB Series 5~15kVA

The advance IGBT inverter, coupled with an isolation transformer, enhances the reliability and load adaptability. This unique construction for input and output isolation provides the advantages of noise rejection as well as clean and safe neutral line to the load, enables PB UPS to be used with critical load applications.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • True Online Double Conversion design for uninterrupted and stable power
  • Output Isolation Transformer for enhanced safety and noise isolation
  • Wide input voltage range for reliable operation during mains fluctuations
  • User-friendly digital LCD display for real-time system monitoring
  • Cold start function for battery start-up without mains supply
  • High crest factor design to support non-linear and high inrush loads
  • Advanced battery management system for extended battery life
  • Inbuilt high-rated charger supporting 2–10 hours of battery backup
  • IGBT-based smart charger for efficient charging and improved input power factor

MODEL PB1105L10 PB1105L16 PB1105B16 PB1106L16 PB1106B16 PB1108L16 PB1110L16 PB1115L16
Capacity (kVA) 05 06 08 10 15
INPUT
Voltage Range 160V~280V AC, Single Phase (3 Wire, L+N+PE)
Frequency Range (Hz) 50Hz ±10%
OUTPUT
Power Factor 0.8 (Standard), 0.9 (Optional)
Voltage (V) 220V / 230V / 240V ±1% (L+N+PE)
Frequency (Hz) 50Hz ±0.1%
Waveform Pure Sine Wave
THDv ≤1%
Efficiency 93.0%
Overload 110-125% for 10 Min, 125-150% for 60 Sec, >150% for 1 Sec.
Isolation Transformer Inbuilt Isolation Transformer
BATTERY
Battery Voltage 120V DC 192V DC (168V and 180V DC Optional)
Charging Current (Max) 1A ~ 10A Standard (High Rating Optional)
Charging Time 4-5 Hrs. to 95%
SYSTEM FEATURES
Display LCD Input and Output Voltage, Input and Output Frequency, Load & Battery %
LED Mains, AC Mode, DC Mode, Low Battery and Overload
Alarm Battery Low Voltage, Abnormal Power Supply, UPS Failure, Overload
Protection Battery Low Voltage, Overload, Short Circuit and Over/Voltage
ENVIRONMENT
Temperature Operating: 0~50°C*, Storage: -15°C ~ 60°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise ≤45dBA ≤50dBA
STANDARD
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS
Safety IEC/EN62040-1
EMC / Protection IEC/EN62040-2, IEC/EN62040-3, Complying to CE
PHYSICAL
Dimension WxDxH (mm) 250x550x500 250x550x680 250x550x500 250x550x680 280x615x685 350x650x785
Weight (Kg) 54 51 98 52 99 73 76 104
COMMUNICATION INTERFACE
Optional SNMP / ModBus / Dry Contact / USB / RS-485 / RS-232
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000