MFX Series 1~10kVA

A true online double-conversion UPS with PWM technology and fully digitized microprocessor control provides high-frequency, pure sine wave output. It ensures constant voltage and frequency (CVCF), features an LCD display, wide input voltage range, high input power factor (≥0.99), and includes static bypass and cold start functions for reliable performance.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • True Online Double Conversion, PWM Technology.
  • Fully Digitized Microprocessor Control, High Frequency, Pure Sine Wave Output.
  • CVCF (Constant Voltage Constant Frequency)
  • LC Display and Wide Input Voltage Range
  • High Input Power Factor ≥0.99
  • Static Bypass and Cold Start
  • IGBT Based - Inverter & Rectifier
  • In-built Isolation Transformer
  • Inbuilt Advanced Battery Management
  • Automatic Battery Charge in UPS Off Mode
  • EMI/RFI and Noise Filter
  • Generator and Solar Compatible
  • High Reliability Digital Control
  • Auto-start Function
  • ECO Mode

MODEL MFX1101L3 MFX1102L4 MFX1102L6 MFX1102L8 MFX1103L6 MFX1103L8 MFX1105L16 MFX1106L16 MFX1110L16
Capacity 1 kVA 2 kVA 3 kVA 5 kVA 6 kVA 10 kVA
INPUT
Nominal Voltage 220V/230V/240V AC (1Ph+N+PE, 3 Wire)
Operating Voltage Range 110V~300V AC Load Dependent
Operating Frequency Range 50 / 60 Hz ± 10% (Auto Sensing)
Power Factor >0.99
OUTPUT
Output Voltage/Power Factor 220V / 230V / 240V AC / ±1% / 0.8 Std., 0.9 Optional
Output Frequency Auto Sensing 50 / 60 Hz ± 1±10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
Harmonic Distortion (THDv) ≤1%
Crest Factor 3:1
Efficiency 94.0% Dual Conversion Mode, 99.0% ECO Mode
BATTERY
DC Voltage 36V 48V 72V 96V 72V 96V 192-240V Configurable
Charge Current 6.5 A Configurable
Typical Recharge Time 4-5 Hours (90% of full capacity)
SYSTEM FEATURES
LCD Indication Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation Mode such as “On Line”, “ON Batt” or On “Bypass”, Fault Codes, Battery & Load Bar graph.
LED Indication Normal Operation, Bypass, Abnormal, Fault and Battery Mode
Alarms / Protection Batt. Low, DC High, Inverter Under/Over Voltage, UPS Overload, Short Circuit, Fan Failure and UPS Fault.
Overload Capability ≤ 125% for 10 min, >125-150% for 1 min, >150% for 200 ms
Transfer Time AC to Battery : 0ms, Inverter to Bypass : 4ms (Typical)
ENVIRONMENTAL
Temperature Operating: 0~50°C*, Storage: -15°C ~ 60°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise <55dBA
PHYSICAL
Dimension WxDxH (mm) 144x400x350 145x385x360 285x455x600 220x481x610
Weight (Kg) 7.4 12.7 12.8 13.7 12.8 13.7 20.8 21.5 24.5
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
COMMUNICATION INTERFACE
Standard RS-232
Optional SNMP / ModBus / Dry Contact / USB / RS-485
Monitoring Software NetAgent Utility v5.8 / UPSilon 2000