| MODEL |
GTP33120L32 |
GTP33160L32 |
GTP33200L32 |
GTP33250L32 |
| Capacity (KVA) |
120 |
160 |
200 |
250 |
| INPUT |
| Nominal Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Voltage Range |
305 - 478V AC |
| Frequency Range |
50 / 60 Hz ± 10% Auto Sensing |
| Power Factor |
≥ 0.99 |
| Harmonic Distortion (THDi) |
≤ 3% |
Bypass Range |
Voltage |
380 V AC Max. Voltage: +25% (Optional +10%, +15%, +20%)
400V AC Max. Voltage: +20%(Optional +10%, +15%)
415V AC Max. Voltage: +15% (Optional +10%)
Min. Voltage: -45% (Optional -20%, -30%)
|
| Frequency |
± 10% (Configurable) |
| Generator Input |
Support |
| OUTPUT |
| Output Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Voltage Regulation |
± 1% |
| Power Factor |
0.9 (Standard) & Unity (Optional) |
0.9 |
| Frequency |
Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1Hz Battery Mode |
| Crest Factor |
3:1 |
| Harmonic Distortion (THDv) |
≤ 2% |
| Overload |
≤ 125% for 10 Min, ≤ 150% for 1 Min, ≥ 150% for 200 ms |
| Efficiency |
96.5% Dual Conversion Mode, 99% ECO Mode |
| BATTERY |
| Battery Voltage |
360 - 600 VDC |
| SYSTEM FEATURES |
| Transfer Time |
Zero |
| Self-Diagnostics / EPO |
Upon Power On and Software Control / Inbuilt |
| IP Protection |
IP 20 |
| Alarm / Protection |
Line Failure, Battery Low, Overload, System Fault and Short Circuit |
| Display |
LED |
Line Mode, Bypass Mode, Battery Low, Overload and UPS Fault Codes |
| LCD |
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load %, Battery Voltage & Temperature, Output W/VA |
| Parallel |
Inbuilt |
| ENVIRONMENT |
| Temperature |
Operating: 0~50°C; Storage: -25°C ~ 55°C |
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M |
| Noise |
<60dBA |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS |
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE |
| PHYSICAL |
| Dimension WxDxH (mm) |
442 x 850 x 1200 |
| Net Weight (Kg) |
170 |
205 |
220 |
270 |
| COMMUNICATION INTERFACE |
| Standard |
RS-232 |
| Optional |
SNMP / ModBus / Dry Contact / USB / RS-485 |
| Monitoring Software |
NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 |