| MODEL |
MFP1105L16 |
MFP1106L16 |
MFP1110L16 |
| Capacity (kVA / kW) |
05 / 05 |
06 / 06 |
10 / 10 |
| INPUT |
| Nominal Voltage |
220V / 230V / 240V AC (L+N+PE) |
| Operating Voltage Range |
110V~300V AC Load Dependent |
| Operating Frequency Range |
50 / 60 Hz ± 10% (Auto Sensing) |
| Power Factor |
0.99 |
| Bypass |
Voltage |
± 20% (Configurable) |
| Frequency |
± 10% (Configurable) |
| ECO Range |
Same as the Bypass, can be configured |
| Generator Input |
Compatible |
| OUTPUT |
| Rated Voltage |
220V / 230V / 240V AC L+N+PE (Configurable) |
| Power Factor |
0.8 (Standard) 0.9 / 1.0 (Optional) |
| Voltage Regulation |
±1% |
| Frequency |
Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode |
| Crest Factor |
3:1 |
| Overload |
≤ 125% for 10 Min, ≤ 150% for 30 Sec, ≥ 150% for 200ms |
| Harmonic Distortion (THDv) |
≤1 |
| Efficiency |
94.0% Dual Conversion Mode, 99.0% ECO Mode |
| BATTERY |
| Battery Voltage |
192V DC / 216V & 240V DC (Configurable) |
| Typical Recharge Time |
4-5 Hours to 90% of full Capacity |
| Charge Current |
6A |
10A |
| SYSTEM FEATURES |
| IP Protection |
IP 20 |
| Transfer Time |
Zero |
| EPO / ECO / CVCF |
Shutdown UPS Immediately / ECO and CVCF Mode can be Configurable |
| Alarm / Protection |
Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC BUS Under / Over Voltage and Battery low
|
| LED Display |
Line Mode, Backup Mode, ECO Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
| LCD Display |
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery
Voltage, Temperature & Remaining Battery Backup Time, Load VA/W, Load and Battery Bargraph
|
| ENVIRONMENTAL |
| Temperature |
Operating: 0~50°C*, Storage: -15°C ~ 60°C |
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M |
| Noise |
≤ 45dBA |
| PHYSICAL |
| Dimension WxDxH (mm) |
192x465x345 |
192x540x345 |
| Net Weight (Kg) |
12 (L), 58 (B) |
14 (L), 68(B) |
| STANDARDS |
| Quality |
ISO 9000, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS |
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE |
| COMMUNICATION INTERFACE |
| Standard |
RS-232 |
| Optional |
SNMP / ModBus / Dry Contact / USB / RS-485 |
| Monitoring Software |