MODEL
|
UGX3360L32
|
UGX3380L32
|
UGX33100L32
|
|
Capacity (kVA)
|
60
|
80
|
100
|
|
INPUT
|
|
Nominal Voltage
|
380V / 400V / 415V AC (3Ph+N+PE)
|
|
Voltage Range
|
+25% - 35%
|
|
Frequency Range
|
50 / 60 Hz ± 20% Auto Sensing
|
|
Power Factor
|
≥ 0.99
|
|
Harmonic Distortion (THDi)
|
≤ 2%
|
Bypass Range
|
Voltage
|
35% (Optional -20%, -30%)
|
|
Frequency
|
± 10% (Configurable)
|
|
Generator Input
|
Support
|
|
OUTPUT
|
|
Output Voltage
|
380V / 400V / 415V AC (3Ph+N+PE)
|
|
Voltage Regulation
|
± 1%
|
|
Power Factor
|
1.0
|
|
Frequency
|
Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
|
|
Crest Factor
|
3:1
|
|
Harmonic Distortion (THDv)
|
≤ 2%
|
|
Overload
|
≤125% for 10 Min, ≤ 150% for 1 Min, ≥ 150% for 200 ms
|
|
Efficiency
|
96.5% Dual Conversion Mode, 99% ECO Mode
|
|
BATTERY
|
|
Battery Voltage
|
300 - 600 VDC
|
|
SYSTEM FEATURES
|
|
Transfer Time
|
Zero
|
|
Self-Diagnostics / EPO
|
Upon Power On and Software Control / Inbuilt
|
|
IP Protection
|
IP 20
|
|
Alarm / Protection
|
Line Failure, Battery Low, Overload, System Fault and Short Circuit
|
|
Display
|
LED
|
Line Mode, Bypass Mode, Battery Low, Overload and UPS Fault Codes
|
|
LCD
|
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load %, Battery Voltage & Temperature, Output W/VA
|
|
Parallel
|
Inbuilt
|
|
ENVIRONMENT
|
|
Temperature
|
Operating: 0~50°C*, Storage: -10°C ~ 55°C
|
|
Humidity / Altitude
|
0~95% RH Non-condensing / <1500 M
|
|
Noise
|
<60dBA
|
|
STANDARDS
|
|
Quality
|
ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
|
|
Safety
|
IEC/EN62040-1
|
|
EMC / Performance
|
IEC/EN62040-2; IEC/EN62040-3, Complying to CE
|
|
PHYSICAL
|
|
Dimension WxDxH (mm)
|
500x580x655
|
884x850x1200
|
|
Net Weight (Kg)
|
124
|
227
|
264
|
|
COMMUNICATION INTERFACE
|
|
Standard
|
RS-232
|
|
Optional
|
SNMP / ModBus / Dry Contact / USB / RS-485
|
|
Monitoring Software
|
NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000
|