| MODEL |
PSM3316L32U2 |
PSM3320L32U2 |
PSM3325L32U2 |
PSM3330L32U2 |
PSM3325L32U2 |
| Module Rating |
16kVA |
20kVA |
25kVA |
30kVA |
32kVA |
| Dimension WxDxH (mm) |
440×620×86 (2U) |
| Weight (Kg) |
21 |
| INPUT |
| Nominal Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Operating Voltage Range |
228V - 480V AC Load Dependent |
| Operating Frequency Range |
40Hz - 70Hz Auto Sensing |
| Power Factor |
≥ 0.99 |
| Harmonic Distortion (THDi) |
≤ 3% |
| Generator Input / Walking |
Support / 0-40 Sec. (Configurable) |
| OUTPUT |
| Output Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Voltage Regulation |
± 1% |
| Power Factor |
1.0 (Unity) |
| Frequency |
Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
|
| Crest Factor |
3:1 |
| Harmonic Distortion (THDv) |
≤ 1% |
| Over Load |
≤ 125% for 10 min, ≤ 150% for 1 min, > 150% for 200 ms
|
| Efficiency |
96.8% Dual Conversion Mode, 99% ECO Mode
|
| BATTERY |
| Battery Voltage |
± 240V DC Nominal (30 - 50 Nos. Configurable)
|
| SYSTEM FEATURE |
| Self-Diagnostics |
During Power ON and Software Control |
| EPO |
UPS Shut down |
| Transfer Time |
Zero |
| Alarm / Protections |
Short Circuit, Input Under/Over Voltage, Over Temperature,
Over Load, DC BUS Under / Over Voltage and Battery low
|
| Display |
Touch Screen LCD & LED Indication |
| ENVIRONMENTAL |
| Temperature |
Operating: 0~50°C*, Storage: -15°C ~ 55°C |
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M |
| Noise |
<55dBA |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS
|
| Safety |
OHSAS 18001, IEC/EN62040-1
|
| EMC / Performance |
Complying to CE, IEC/EN62040-2; IEC/EN62040-3
|
| COMMUNICATION INTERFACE |
| Standard |
Rack: RS-232, RS-485, Dry Contact |
| Optional |
BMS/ RS485/ LBS / SNMP / ModBus / Dry Contact / Parallel, Dry contact, Relay Card, Battery temperature sensor
|
| Monitoring Software |
NetAgent Utility v5.8 / Muser 4000 / Power Manager
|