| Model |
MFILVX02L1B50 |
MFILVX03L1B50 |
MFILVX05L1B100 |
MFILVX10L2B100 |
MFILVX15L3B100 |
MFILVX20L4B100 |
MFILVX25L5B100 |
MFILVX30L6B100 |
| Capacity (kVA) |
2 |
3 |
5 |
10 |
15 |
20 |
25 |
30 |
| No. of UPS Modules |
1 |
2 |
3 |
4 |
5 |
6 |
| INPUT |
| Nominal Voltage |
230V AC (1Ph+N+PE, 3 Wire) |
230V AC (1Ph+N+PE, 3 Wire)/ 400V AC (3Ph+N+PE, 5 Wire) |
| Operating Voltage Range |
110V~280V AC (P-N) Load Dependent |
Operating Frequency Range |
50 / 60 Hz ± 10% (Auto Sensing) |
| Power Factor |
≥ 0.99 |
| OUTPUT |
| Output Voltage |
230V AC |
230V AC/ 400V AC |
| Voltage Regulation |
± 1% |
| Power Factor |
Unity |
| Frequency (Battery Mode) |
50/60 Hz ± 0.1Hz |
| Crest Factor |
3:1 |
Harmonic Distortion (THDv) |
≤ 2% |
| Efficiency |
94.0% Dual Conversion Mode, 99.0% ECO Mode |
| BATTERY |
Max. Charging Current (Configurable) |
60A |
120A |
180A |
240A |
300A |
360A |
| Battery Voltage |
48V DC |
| Battery Chemistry |
LiFePO4 |
Maximum Discharge Rate |
1.0C |
| No. of Battery Modules |
1 |
2 |
3 |
4 |
5 |
6 |
| Battery Energy |
2.4kWh |
4.8kWh |
9.6kWh |
14.4kWh |
19.2kWh |
24kWh |
28.8kWh |
| Expendable Battery Pack |
10 |
5 |
4 |
3 |
2 |
| Battery Backup Time |
1~5 hours (depends on the connected load) |
| Recharge Time (Typical) |
2 Hours (Approx.) |
| SYSTEM FEATURES |
| LCD Indications |
Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA/%, Operation Mode such as "On Line", "On Batt" or "On Bypass", Fault Codes,
Battery & Load Bar graph
|
| LED Indications |
Normal Operation, Bypass, Abnormal, Fault and Battery Mode |
| Alarm / Protection |
Batt. Low, DC High, Inverter Under/Over Voltage, UPS Overload, Short Circuit, Fan Failure and UPS Fault |
| Transfer Time |
AC to Battery: Zero, Inverter to Bypass: 4ms (Typical) |
| Overload Capability |
105-150% for 10s, >150% for 5s |
| Degree of Protection |
IP20 |
| ENVIRONMENT |
| Temperature |
Operating |
0~50°C (No-Derating) |
| Storage |
-15°C~ 60°C |
| Humidity |
0~95% RH Non-condensing |
| Altitude |
<1500M |
| Noise |
<55dBA |
| COMMUNICATION INTERFACE |
| Standard |
RS-232/ USB/ EPO |
| Optional |
SNMP/Dry Contact/ModBus/IoT |
| Monitoring Software |
BPE Cyber/ UPSilon 2000 |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS |
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE |