CP Series 5~20kVA

True Online Double Conversion Topology Output Isolation Transformer Wide Input Voltage Range User Friendly Digital LC Display

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • True Online Double Conversion Topology
  • Output Isolation Transformer
  • Wide Input Voltage Range
  • User Friendly Digital LC Display
  • Cold Start Function
  • High Crest Factor Circuit Design
  • Advance Battery Management
  • Improved Input Power Factor
  • Inbuilt High-Rated IGBT based charger enable long battery backup up

Rear Panel

  1. RS232 / SNMP (Optional)
  2. Fans
  3. Battery Breaker
  4. Output Terminal
  5. Battery Terminal
  6. Input Breaker
  7. Maintenance Bypass Breaker
  8. Input Terminal

Overview:
  • Wide input frequency range ensures all types of fuel generators compatibility.
  • Optimization of high performance battery.
  • Advanced charging technology maximises the activation of the battery, i.e saves the charging time and extends the battery life.
  • Battery cold start function.
  • The UPS can be started directly by battery group when no utility power.
  • Comprehensive and reliable protection
  • self-diagnosis function before startup, avoids the risks that the failure may lead.
  • The multi-protections such as over load , short circuit , over temperature. battery under voltage, battery over voltage ensure the system stability and reliability.
  • Solar compatibility (Optional)
  • Static bypass (Optional)

MODEL CP3305L16 CP3310L20 CP3315L20 CP3320L20 CP3320L30
Capacity 5 kVA 10 kVA 15 kVA 20 kVA
INPUT
Voltage Range 320V ~ 480V AC, Three Phase (4 Wire)
Frequency Range (Hz) 50 / 60 Hz ±10%
Power Factor >0.95
OUTPUT
Power Factor 0.8 (Standard) 0.9 (Optional)
Voltage (V) 400V AC
Frequency (Hz) 50Hz ± 0.1%
Waveform Pure Sine Wave
Efficiency 94.0%
THDv ≤1%
Overload ≤110% for 60 Min, ≤125% for 10 Min, ≤150% for 1 Min and ≥150% for 300 ms
Isolation Transformer Inbuilt Isolation Transformer
BATTERY
Battery Voltage 192V 240V 360V
Charging Current (Max) 1A ~ 10A Standard (High Rating Optional)
Charging Time 4-5 Hrs. for 95%
SYSTEM FEATURES
Display LCD Input and Output Voltage, Input and Output Frequency, Load & Battery %
LED Mains, AC Mode, DC Mode, Low Battery, Overload
Alarm Battery Low Voltage, Abnormal Power Supply, UPS Failure, Overload
Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC BUS Under / Over Voltage and Battery low
ENVIRONMENTAL
Temperature Operating: 0~50°C*, Storage: -15°C ~ 60°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise <50dBA
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC / Protection IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
Dimension WxDxH (mm) 280x615x685
Weight (Kg) 160 170 180 185 225
COMMUNICATION INTERFACE
Optional SNMP / ModBus / Dry Contact / USB / RS-485 / RS-232
Monitoring Software NetAgent / UPSilon 2000